Flow rate common value in the pipe

zhaozj2021-02-16  59

Source: http://www.gpszx.com/neteaseivp/resource/paper/detail.jsp? Pk = 631

GPSZX excerpt

Summary: Common value of flow rate in pipeline Key words: pipeline flow rate

Common value of flow rate in the pipeline (m / s)

Fluid species

Application occasion

Pipeline type

Average flow rate

Note

water

Generally give the main pressure pipeline

2-3

Low voltage pipeline

0.5-1

Pump import

0.5-2.0

Pump outlet

1.0-3.0

Industrial water

Centrifugal pump pressure tube

3-4

Centrifugal pump water pipe DN250

1-2

DN250

1.5-2.5

Recurrent pump pressure tube

1.5-2

Reciprocating pump water absorbing pipe

<1

Water supply

1.5-3

Drainage pipe

0.5-1.0

Cooling cold water pipe

1.5-2.5

Hot water pipe

1-1.5

Condensate condensate pump water pipe

0.5-1

Condensate pump outlet pipe

1-2

Self-coating tube

0.1-0.3

General liquid low viscosity

1.5-3.0

High viscosity liquid viscosity 50MPa.sdn25

0.5-0.9

DN50

0.7-1.0

DN100

1.0-1.6

Viscosity 100MPa.sdn25

0.3-0.6

DN50

0.5-0.7

DN100

0.7-1.0

DN200

1.2-1.6

Viscosity 1000MPa.sdn25

0.1-0.2

DN50

0.16-0.25

DN100

0.25-0.35

DN200

0.35-0.55

Gas low pressure

10-20

high pressure

8-15

20-30MPa

Exhaust pipe

2-7

Compressed air compressor compressor intake pipe

-10

Compressor gas pipe

-20

General situation DN <50

<8

DN> 70

<15

Saturated steam boiler, steam turbine DN <100

15-30

DN = 100-200

25-35

DN> 200

30-40

Overheated steam boiler, steam turbine DN <100

20-40

DN = 100-200

30-50

DN> 200

40-60

转载请注明原文地址:https://www.9cbs.com/read-16181.html